Regitec Inverter
Dispositivi Supportati
Il SmartgridOne Controller supporta gli inverter ibridi Regitec sia tramite Modbus TCP (Ethernet) che Modbus RTU (RS485).
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Regitec Hybrid Inverter | ✅ | ✅ |
Cablaggio
Ethernet
Per un cablaggio ethernet corretto: seguire le linee guida per il cablaggio ethernet.
RS485
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| A | RS485 A | RS485_POS | RS485 A | TX+ |
| B | RS485 B | RS485_NEG | RS485 B | TX- |
| GND | RS GND | GND | Not available | G |
Nota
Nota
Assicurarsi che la resistenza di terminazione sia impostata correttamente se l'inverter si trova alla fine del bus RS485.
Avviso
Avviso
Il driver Regitec è configurato rigorosamente per una baud rate di 9600. Assicurarsi che l'inverter non sia impostato a 19200 o 115200, poiché ciò impedirebbe la comunicazione.