Control problems
Always check this first
Tip
You can check off the boxes.
Note
See also "" and "".
You can check off the boxes.
See also "" and "".
By default, a safety factor of 90% is applied, meaning that the SmartgridOne Controller controls everything, including solar production, to be within 90% of the set grid limits. You can change this in the "Advanced Settings" menu (all the way to the bottom of the "Settings" menu). This safety factor helps safeguarding against exceeding the limits, by leaving some room for the controller to react to power fluctuations (e.g. clouds flying over can make the PV production dip by as much as 80%). If you have a combination of consumers and producers, then it is recommended to leave this to 90%. Only set this to 100% if you are sure that there is no risk of tripping breakers or big fluctuations leading to exceeding the limits.
This can happen because of several factors:
A combined accuracy of 2% of the biggest device's nominal power may typically be expected.
There are several reasons why the batteries may not (dis)charge at the same power as the inverter:
What you can check too:
This is an indication of an unbalance between the cells of the batteries. This issue is often solved by force charging the battery to 100% for several hours. To balance the battery cells:
The SmartgridOne Controller stops discharging at 1% above the minimum state of charge. This is because of the following protection mechanism that is used to prevent the battery from completely draining due to self discharging: The SmartgridOne Controller will send a signal to the battery to charge at a small amount as soon as the state of charge drops to 1% below the minimum state of charge due to self discharge of the battery. This charge signal is maintained until the battery is at 1% above the minimum state of charge. The SmartgridOne Controller charges the battery 2% and not 1%, to prevent that an unstable measurement of the state of charge would cause continuous switchovers between charging and not charging. (If your battery is in reality at 4.99%, then it might report as 4%, which would cause charging, and quickly it would go to 5.00%, stop charging, drop back to 4.99% in a small time, start charging again, and so on.)
Settings to check:
By default, a safety factor of 90% is applied, meaning that the SmartgridOne Controller controls everything, including solar production, to be within 90% of the set grid limits. You can change this in the "Advanced Settings" menu (all the way to the bottom of the "Settings" menu). This safety factor helps safeguarding against exceeding the limits, by leaving some room for the controller to react to power fluctuations (e.g. clouds flying over can make the PV production dip by as much as 80%). If you have a combination of consumers and producers, then it is recommended to leave this to 90%. Only set this to 100% if you are sure that there is no risk of tripping breakers or big fluctuations leading to exceeding the limits.
EV charging stations only accept maximum charging currents. Most likely the SmartgridOne Controller does send full power as the maximum charge current, but the EV might decide on its own not to use this. The effective charging speed is especially likely to be lower if the EV is almost full.
The default states of the relay are:
Please note that this only sets what the relay does by default. Relay control always stays active.
Yes, you can use the external API for this purpose. TODO: add link